The earthing for array and LT power system shall be made of 3.0 m long 40 mm diameter perforated GI pipe / chemical compound filled, double walled earthing electrodes including accessories, and providing masonry enclosure with cast iron cover plate having pad-locking arrangement, watering pipe using charcoal or coke and salt as required as per provisions of IS: 3043. v. Necessary provision shall be made for bolted isolating joints of each earthing pit for periodic checking of earth resistance. Each string/ array and MMS of the plant shall be grounded properly. The array structures are to be connected to earth pits as per IS standards. Necessary provision shall be made for bolted isolating joints of each earthing pit for periodic checking of earth resistance. vi. The complete earthing system shall be mechanically & electrically connected to provide independent return to earth. For each earth pit, a necessary test point shall be provided. vii. In compliance to Rule 11 and 61 of Indian Electricity Rules, 1956 (as amended up to date), all non-current carrying metal parts shall be earthed with two separate and distinct earth continuity conductors to an efficient earth electrode. viii. Unless otherwise specified, the earthing system primary and secondary grid conductors, equipment connections shall be constructed with galvanized iron flat. However the earthing of transformer neutrals, PLC and inverter terminals and electronic earthing shall be provided using copper earthing conductor only. ix. Earthing Mesh is to prepared and installed in entire power plant. Each PV Module frame shall be earthed in accordance with module manufacturer guidelines. In case module frame earthing is to be separately provided, it shall be earthed with minimum 2.5 sq. mm flexible Copper Cables with lug at suitable location of module frame and
Submit Your Enquiry